ZiyangSynergy POE SE T series screw machine special synthetic refrigerator lubricant
Synergy POE SE T series adopts synthetic ester as base oil and is compounded with extreme pressure, antioxidant, corrosion resistance and other additives. It is especially suitable for open and semi-closed R22 industrial screw refrigeration units.
Category:
ZiyangSynthetic refrigeration lubricating oil
Product Description
Synergy POE SE T series adopts synthetic ester as base oil and is compounded with extreme pressure, antioxidant, corrosion resistance and other additives. It is especially suitable for open and semi-closed R22 industrial screw refrigeration units.
Performance characteristics
1. Excellent thermal oxidation stability, to prevent the deterioration of lubricating oil under high temperature;
2. Mixed with R22 has excellent dissolution characteristics;
3. Good material adaptability to avoid leakage in the use of the system;
4. Excellent low temperature performance, very low pour point, excellent low temperature fluidity, to ensure that the system to adapt to a variety of low temperature applications;
5. Excellent high and low temperature performance to ensure the normal operation of the system in a wide temperature range;
6. Good lubricity, protect the refrigeration compressor and reduce wear;
7. Excellent comprehensive performance, to ensure the normal work of the refrigeration system for a long time.
Product Application
1. This product can be widely used in the use of hydrochlorofluorocarbon (R22) as the refrigerant refrigeration system, applicable compressor type reciprocating, screw chiller, including cold storage, industrial air conditioning and heat pump, central air conditioning, chiller;
2.SE 85T various types of industrial centrifugal refrigeration units, screw refrigeration units, etc;
3.SE 150T and SE 220T applicable temperature range:-40~150 ℃;
4.SE 320T Applicable temperature range:-35~150 ℃;
5. Short-term operation at 170 ℃ is acceptable.
Precautions
1. Do not mix with other lubricants, physical or chemical reactions may occur between different lubricants, resulting in a significant decline in performance;
2. Timely cover after use to avoid the mixing of moisture, dust and other impurities;
3. When using the lubricating parts in contact with rubber, plastic, paint and other non-metallic materials, the material compatibility test should be carried out in advance.
packing form
20L drum, 200L drum or according to customer demand for packaging.
Typical data| Analysis Project | 40°C Kinematic viscosity mm²/s | Acid value mgKOH/g | Flash Point ℃ | Pour point ℃ | Water content ppm | Corrosion (T2Cu100 ℃,3h) | Insulation strength kV | Critical solution temperature (10% of R22)℃ |
| Test Method | GB/T 265 | GB/T 7304 | GB/T 267 | GB/T 3535 | GB/T 11133 | GB/T 5096 | GB/T 507 | SH/T 0699 |
| SE 85T | 81.2 | 0.02 | 221 | -42 | 50 | 1b | 35 | <-40 |
| SE 150T | 151.3 | 0.05 | 248 | -43 | 50 | 1b | 35 | <-40 |
| SE 220T | 221.5 | 0.05 | 249 | -42 | 50 | 1b | 35 | <-40 |